2-wire RTD Temperature Transmitter for Head-mounting Type
● Linearised temperature measurement with PT100 sensor
● To avoid temperature signal attenuation during long
distance transmission, it converts PT100 into standard
analog current output 4~20 mA DC ( 2 -wire )
● A stable and accurate figure can be collected and shown
on the display of terminal instrument. The instrument
includes PLC, digital display,industrial computer, ect.
INPUT
Input.......................................................................PT 100Ω (3-wire)
Cable resistance .............≤ 50 Ω (3 wires with the same resistance)
PT100Ω sensor current .......................................................< 0.8mA
ZERO adjustment range .........................................................±10 %
SPAN adjustment range(TP01) ..............................................±10 %
OUTPUT
Output ....................................................................4~20 mA ; 2-wire
Accuracy .................................................................... ±0.1 % of F.S.
Load resistance ........................... ≤ (supply voltage - 8 V) / 0.02A Ω
Load resistance stability ........................................... ±0.05% / 100Ω
Power supply stability ................................................... ±0.025% / V
Temperature drift ..................................................< ±0.015% fs / °C
Calibration temperature ......................................................20~28°C
Response time................................................................... < 250 ms
PROTECTION
PT100Ω signal disconnection protection & output ............................
.............................................................................................. >23mA
PT100Ω signal short circuit, protection & output ..............................
................................................................................................< 3mA
Output polarity protection ...........................................................Yes
ELECTRICAL SPECIFICATION
Power supply ................................................................. 10~30 VDC
Working temperature ........................................................ -20~60°C
Working humidity ........................................... 0~95% rh (non-cond.)
Protection degree ..............................housing: IP30 ; terminal: IP00
Housing .....................................................................................ABS
Weight ........................................................................................40g